BIOSYSTEMS GAS DETECTION EQUIPMENT

The biosystems gas detection equipment shall have all of its components, including the controller, RS-485 communication module and relay outputs boards in a single enclosure. Multiple enclosures requiring inter-wiring are not acceptable.

The Control Panel shall incorporate the necessary logic circuits to operate the exhaust/supply fans and the motorized dampers for fresh air and/or exhaust according to the specified logic of ventilation. For example, if the biosystems gas detection equipment operated by the 100 PPM CO contacts does not reduce the CO level below this value within 30 minutes (3 to 60 minutes adjustable), the Control Panel shall go on visual and audible alarm and also provide a contact for remote alarm indication or supervision.